Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03970
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
12/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ARC SHIELDS TO BE APPROVED BY AHJ AND LISTED 2) USE APPROVED HARDWARE WITH DEVICES 3) BROKEN FIXTURE WHIP 4) NEED GASKET FOR FLOOR BOX FOR WATER EXTRUTIONS 5) MENS RESTROOM EM LIGHT NOT WORKING 6) NEED DISCONNECTING MEANS AT FIXTURES 410.63 (G) 7) PENDANT LIGHTING FIXTURES TO BE WRENCH TITE 8) FINISH BONDING AT XFMR AS DISCUSSED |
|
12/21/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 2) IDENTIFY IG GROUNDING CONDUCTOR 3) MAIN BONDING JUMPER AND GROUNDING ELECTRODE CONDUCTOR TO TERMINATE SAME LUG-XFMR 4) SEAL ENTRANCE ABOVE CURRENT CARRING PARTS AT MAIN SWITCHBOARD ROOF: 1) BOND BUSHINGS OVER 250V 250.97 2) ONLY ONE CONDUCTOR PER LUG 3) VERIFY ACCESS PANEL TO A/C PER 440.14 4) LOOSE FITTINGS |