Permit: T08CM03955

Parcel: 141153570

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03955

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR CEILING TILES
05/19/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DRYER VENT SECTION INSTALLED UPSIDE DOWN
2. 1 JOINT NOT SEALED
3. PROVIDE THE COMPLETE DUCT SYSTEM AS PER PLANS
4. RETURN DUCTS MISSING TO EXAM ROOMS, RETURN DIFFUSERS USED IN PLACE OF SUPPLY DIFFUSERS IN SOME AREAS.
5. RETURN MISSING IN STERILIZATION ROOM.