Permit: T08CM03955

Parcel: 141153570

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM03955

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/10/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE HANGERS IN ALIGNMENT WITH PIPING, AT CORRECT INTERVALS FOR VENT & WATER SYSTEM - SEAL INSULATION INSTALL CLOSET FLANGES PER INSTALLATION STANDARD
2006 UPC
04/20/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/17/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
IN WALL DWV AND WATER WITH TEST THRU ROOF OK
1. RECALL FOR CORRECT CLOSET FLANGE INSPECTION PRIOR TO SETTING STOOLS
2. PROVIDE SUPPORT AT CORRECT INTERVALS FOR ABOVE CEILING PIPING
3. ABOVE CEILING INSULATION TO BE SEALED CORRECTLY
4. VACUUM AIR SYSTEM TO BE 3RD PARTY INSPECTED
04/16/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE APPROVED SUPPORT IN WALLS
2. ADD SUPPORT ABOVE CEILING
04/02/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
THIS INSPECTION 03005 - - NOT READY
1. VENT FOR FLOOR SINK TO BE INSTALLED AT ABOVE CENTER LINE OF DRAIN FOR THIS APPLICATION
2. CLEANOUT FOR STOOL IS REQUIRED TO BE ACCESSIBLE WITHOUT REMOVAL OF STOOL
3. PROVIDE REDLINE OF YOUR DRAINAGE SYSTEM ON SITE AT TIME OF INSPECTION OR INSTALL PER APPROVED PLAN.
4. YOUR COMPRESSED AIR SYSTEM DOES NOT MEET PLAN SPEC. AND 2005 NFPA 99-C REQUIREMENTS