Permit: T08CM03955

Parcel: 141153570

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM03955

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/19/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. METAL FLEX TO BE STRAPPED WITHIN 12" OF CONNECTIONS
2. THE WIRES USED FOR SUPPORT TO BE SECURED @ BOTH ENDS
3. SEAL OPEN ENDS AT SPARE RACEWAYS
4. FINISH ALL CEILING WORK. HAVE OPEN BOXES. HAVE UNFINISHED RACEWAYS
5. STRAP EMT WITHIN 3' OF CONNECTIONS
6. LOW VOLTAGE CABLE TO BE SUPPORTED UP & OFF OF CEILING GRID MIN. EVERY 6'
04/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*