Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/19/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. METAL FLEX TO BE STRAPPED WITHIN 12" OF CONNECTIONS 2. THE WIRES USED FOR SUPPORT TO BE SECURED @ BOTH ENDS 3. SEAL OPEN ENDS AT SPARE RACEWAYS 4. FINISH ALL CEILING WORK. HAVE OPEN BOXES. HAVE UNFINISHED RACEWAYS 5. STRAP EMT WITHIN 3' OF CONNECTIONS 6. LOW VOLTAGE CABLE TO BE SUPPORTED UP & OFF OF CEILING GRID MIN. EVERY 6' |
|
| 04/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |