Permit: T08CM03928

Parcel: 12803076A


Addresses:

5660 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/03/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/02/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/30/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. MAKE UP AIR UNIT DOES NOT MEET THE REQUIRED CFM AS SHOWN ON PLANS.
2. PROVIDE STEP LADDER - NEED TO SEE ABOVE CEILING
3. PROVIDE CAPTURE AND CONTAINMENT TEST
4. SUPPORT ELEC. CONDUITS TO COOLER AND EXHAUST FAN
5. NEED TO TEST HEAT SENSOR
6. PROVIDE WATER TO COOLER
7. AIR BALANCE REPORT INADEQUATE