Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/02/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/30/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. MAKE UP AIR UNIT DOES NOT MEET THE REQUIRED CFM AS SHOWN ON PLANS. 2. PROVIDE STEP LADDER - NEED TO SEE ABOVE CEILING 3. PROVIDE CAPTURE AND CONTAINMENT TEST 4. SUPPORT ELEC. CONDUITS TO COOLER AND EXHAUST FAN 5. NEED TO TEST HEAT SENSOR 6. PROVIDE WATER TO COOLER 7. AIR BALANCE REPORT INADEQUATE |