Permit: T08CM03928

Parcel: 12803076A


Addresses:

5660 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/16/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
TEST ON SYSTEM OK
LEFT GAS CARD AT METER

INSTALL ALL GAS APPLIANCE SHUT OFF VALVES, RECONNECT ANSUL VALVE PULL SYSTEM, PROVIDE APPROVED GAS FLEXES AND ATTACH SAFETY CABLES FOR APPLIANCES ON WHEELS.
RECALL FOR FINAL PLUMBING INSPECTION WHEN ALL APPLIANCES ARE CONNECTED.
03/11/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOT HOLDING 10 PSI
DOWN TO 7 PSI
03/03/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CONSULT WITH ERMA VIA PHONE
(ERMA @ 909-6005)
03/02/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CANCELED PER BELINDA
02/25/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST MUST HOLD WITH NO LOSS OF PRESSURE
02/23/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL GAS PIPING PER SIZING ON PLAN
2. INSTALL ALL APPLIANCE SHUT OFF VALVES AND PROVIDE TEST ON ENTIRE GAS SYSTEM WITH TEST GAUGE IN
1/10 POUND INCREMENTS. TEST TO HOLD WITH NO LOSS OF PRESSURE.
3. WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN TO HAVE 1" AIR GAP AT RECEPTOR
4. WATER HEATER REQUIRES A DRAFT HOOD WITH CORRECT VENT CONNECTORS AND VENT THRU ROOF TO BE IN CORRECT DIRECTION OF FLOW