Permit: T08CM03926

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03926

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ENGINEER AND PLANS CALL FOR 2 CIRCUITS TO TRACS
03/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" OR FLUSH IN COMBUSTIBLES 314.20
2. LABEL EQUIPMENT
3. ONLY ONE GROUND CONDUCTOR PER TERMINAL SCREW SHOWCASE STANDS
4. PROPERLY GROUND TRANSFORMER CASE
5. LABEL PANEL DIRECTORY 408.4
6. EM LIGHTS NOT ALL WORKING
7. SWITCHING FOR LIGHTS NOT AS PER PLANS OR LABELING
8. LIGHTS TO HAVE DISCONNECT SWITCHES 410