Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ENGINEER AND PLANS CALL FOR 2 CIRCUITS TO TRACS |
|
| 03/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" OR FLUSH IN COMBUSTIBLES 314.20 2. LABEL EQUIPMENT 3. ONLY ONE GROUND CONDUCTOR PER TERMINAL SCREW SHOWCASE STANDS 4. PROPERLY GROUND TRANSFORMER CASE 5. LABEL PANEL DIRECTORY 408.4 6. EM LIGHTS NOT ALL WORKING 7. SWITCHING FOR LIGHTS NOT AS PER PLANS OR LABELING 8. LIGHTS TO HAVE DISCONNECT SWITCHES 410 |