Permit: T08CM03926

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03926

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. USE APPROVED STRAPPING ON VERTICALS ALONG STUDS
2. SECURE M/C CABLE WITHIN 12" OF CANS
3. PLEASE PROVIDE AUTHORIZATION TO USE M/C CABLE AND PVC CONDUIT FROM ENGINEER
4. SUPPORT VDV CABLING 725.24, 760.24, 800.24
5. FINISH UNDERGROUND AND IN WALLS

OK STUD FRAMED WALLS AND HARD LID AFTER CORRECTIONS AND SUBJECT TO LETTER FOR M/C EXCEPT AS NOTED.