| 08/11/2009 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
| 08/06/2009 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* 1) LOW PRESSURE TEST IN PLACE |
|
| 08/04/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) WORKING IN DENTAL ROOM INSTALLING PIPING TO CEILING OUTLETS |
|
| 08/03/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) INSTALLING OUTLETS FOR SURGERY ROOM (2) |
|
| 06/30/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) LABELING AND SUPPORTS OK 2) NEED TO SEE FINAL CONNECTIONS, VERIFICATION OF TESTING AND 3RD PARTY CERTIFICATION AT LATER DATE |
|
| 06/29/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 10 02 AND WG TO OVERHEAD WITH 150 PSI TEST ? SUPPORTS OK 2) PROVIDE LABELING AND COMPLETE TO OUTLETS AFTER 3RD PARTY OK ON TESTING |
|
| 06/26/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1) PIPING ON WA SYSTEM, ALL PIPING TO CAPS AT OVERHEAD SET UP FOR PURGE AND BRAZING TO BEGIN |
|
| 06/25/2009 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* O2 PIPING INSTALLED WITH CAPS (4) LOCATIONS AT OVERHEADS WITH 150 PSI TEST IN PLACE NOTE: PER THE PRE-CON MEETING HAVE DAILY INSPECTION THROUGHOUT THE INSTALLATION PROCESS |
|