Permit: T08CM03924

Parcel: 13418113C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/14/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/11/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ITEM #2 FROM PREVIOUS INSPECTION ON 8/6/09
08/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SWITCHING OF LIGHT FIXTURES NOT PER PLAN REQUIRES A & B SWITCHING PER IECC 2006. PLEASE INSTALL PER PLANS OR PROVIDE APPROVED REVISION .
2) INSTALL DISCONNECTING MEANS FOR 2 X 4 FIXTURES PER NEC 410.73 G