Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03917
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CABLE BRACING PER MANUFACTURES INSTRUCTIONS IS NEEDED 2. BOND RISERS PER 250.92 3. CONDUCTOR TO ENTER SECTION SERVED 408.3 - CANNOT CROSSOVER 4. NEED LETTER OF TORQUE |
|
03/06/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SERVICE NOT INSTALLED YET |
|
02/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEE NOTES |
|
01/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS, HARD LIDS WEST OF DEMISING WALL |