Permit: T08CM03916

Parcel: 10512024E


Addresses:

4040 N ORACLE RD


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03916

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/27/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. VERIFY IF SERVICE EQUIPMENT IS APPROVED FOR USE
2. EQUIPMENT LABELING CALLS FOR CABLE BRACING OF CONDUCTORS
3. SUPPORT 2" FNMC
4. TRAILERS NEED TO BE CONNECTED
5. TRAILERS NEED GROUNDING ELECTRODE SYSTEMS
NOT FRAMES
6. LABEL SUB-PANEL BREAKERS AND TRAILER BREAKER