Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 03/27/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 03/25/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1. PROVIDE GREASE RECEPTORS ON HOOD AND ROOF TOP EXHAUST FAN 2. WASTE VENT WITHIN 10' OF MAKE UP AIR INTAKE 3. NEED SMOKE CONTAINMENT TEST 4. SECOND LAYER OF FIRE WRAP OK |
|
| 03/23/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 03/20/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* WILL LOOK AT 2ND LAYER AND MUA ON ABOVE CEILING INSPECTION |
|
| 03/18/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1ST LAYER OF FIRE WRAP OK PROCEED WITH SECOND LAYER |
|
| 03/12/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCT. OK FOR 1ST LAYER OF FIRE WRAP |
|
| 03/11/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 03/10/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* PROVIDE SMOKE TEST ON DUCT |