Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03914
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. SPEAKER WIRE REMOVED. IF REINSTALLED MUST BE AS PER CODE 2. RECEPTACLE BEHIND REACH IN FRIDGE TO BE GFCI PROTECTED - 210.8 |
|
05/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT SPEAKER WIRES UP OFF OF GRID 725.24, 300.11 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. TIGHTEN WATER HEATER FITTINGS 4. GROUND AT WATER HEATER - ALL STRANDS UNDER TERMINAL SCREW OR USE TERMINAL END 5. KITCHEN RECEPTACLES TO BE AS PER 210.8(C) AS MARKED ON PLANS 6. WHERE ARE RECESSED CAN LIGHTS: ON PLANS ALSO TRAC LIGHT 7. RECEPTACLE LAYOUT NOT AS PER PLANS ALSO, DISCONNECTS 8. PANEL SCHEDULE TO BE AS PER 408.4 9. SECURE DISCONNECT STRANDS TO ROOF |