Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03914

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. SPEAKER WIRE REMOVED. IF REINSTALLED
MUST BE AS PER CODE
2. RECEPTACLE BEHIND REACH IN FRIDGE TO BE GFCI PROTECTED - 210.8
05/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT SPEAKER WIRES UP OFF OF GRID 725.24, 300.11
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. TIGHTEN WATER HEATER FITTINGS
4. GROUND AT WATER HEATER - ALL STRANDS UNDER TERMINAL SCREW OR USE TERMINAL END
5. KITCHEN RECEPTACLES TO BE AS PER 210.8(C) AS MARKED ON PLANS
6. WHERE ARE RECESSED CAN LIGHTS:
ON PLANS ALSO TRAC LIGHT
7. RECEPTACLE LAYOUT NOT AS PER PLANS
ALSO, DISCONNECTS
8. PANEL SCHEDULE TO BE AS PER 408.4
9. SECURE DISCONNECT STRANDS TO ROOF