Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM03909
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
06/03/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IT IS NOT DONE 2) BALCONY RAIL NO OPENING LARGER THAN 4", DECK TO BOTTOM RAIL 5" 3) 2ND FLOOR BEDROOM MISSING RECEPT DEVICE AND COVER PLATE 4) #2 ABOVE NOT DONE-STOPPED INSPECTION |
|
06/01/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COLOR CODE WIRE IN ALL DISCONNECTING BOXES 2) NEED K/O PLUG WEST A/C DISCONNECT BOX 3) BALCONY RAILING 4) INSTALL DISHWASHER 5) LAUNDRY CIRCUIT CHECK WIRING, WITH TESTER 6) LEAK IN CONDENSATE AT FURN 2ND FLOOR 7) ONLY TWO ARC/FAULT BREAKERS, IN PANEL, NO POWER TO 2ND FLOOR BEDROOMS 8) UNSECURED LIGHT FIXTURE FURNACE ROOM |