Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* AIR BALANCE OK |
|
| 01/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PER MECH. SPEC. 19 SEC.B -- PROVIDE INDEPENDENT BALANCE CONTRACTOR 2. PER MECH. SPEC. 7 SEC. C -- ALL CONDENSATE PIPING TO BE INSULATED WITH 1/2" ARMAFLEX, PROVIDE CALCIUM BLOCKS AT HANGERS 3. DUCT IS SUPPORTED FROM COPPER PIPING, REMOVE AND HANG FROM STRUCTURE 4. PROVIDE OBD's IN SUPPLY AND RETURN GRILLS PER AIR DEVICE SCHEDULE SHEET M1.0 |