Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/27/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECALL WHEN APPROVED REVISION ON SITE ALL OTHER PREVIOUS INSPECTION ITEMS CORRECTED |
|
| 01/22/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/21/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED RECEPTACLE FOR SERVICING OF FAN COIL UNITS TO BE WITHIN 25' 2. MISSING OUTDOOR EM LIGHT 3. HEAT PUMPS NOT CIRCUITED PER PLAN NEED APPROVED REVISION OR INSTALL PER PLAN WILL NEED PROPER PHASE COLORING FOR 480V 4. DO NOT FEED ONE A/C DISCONNECT THROUGH THE OTHER 5. PROVIDE DETAILED PANEL DIRECTORIES |