Permit: T08CM03862

Parcel: 106042070


Addresses:

3367 N GERONIMO AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/30/2011 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/15/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BROKEN COVER STUD
2) BOND SERVICE NIPPLE 250.92
3) VERIFY SUN LIGHT RESISTANT CONDUCTORS
4) PLANS CALL FOR 2 SETS OF 3/0 UNDEGROUND-THIS IS OVERHEAD-CANNOT DETERMINE CONDUCTOR MARKING FOR SIZE OR MARKINGS
5) BOND CONDUCTOR TO BE PER 250.64 (E)
6) CANNOT INSTALL COVER SCREWS
7) CANNOT OPEN SECOND PANEL COVER
8) LABEL BREAKERS