Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/15/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BROKEN COVER STUD 2) BOND SERVICE NIPPLE 250.92 3) VERIFY SUN LIGHT RESISTANT CONDUCTORS 4) PLANS CALL FOR 2 SETS OF 3/0 UNDEGROUND-THIS IS OVERHEAD-CANNOT DETERMINE CONDUCTOR MARKING FOR SIZE OR MARKINGS 5) BOND CONDUCTOR TO BE PER 250.64 (E) 6) CANNOT INSTALL COVER SCREWS 7) CANNOT OPEN SECOND PANEL COVER 8) LABEL BREAKERS |