Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03850
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/12/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PLANS DO REQUIRE 1 1/2" INSULATION ON ALL ROUND DUCT. 2. SEE NOTE "R" PAGE M2. 3. INSULATION REQUIREMENTS HAVE BEEN MET. 4. OK TO PROCEED WITH SHEETROCK. 5. PROVIDE A LIGHT & RECEPTACLE FOR SERVICING FAN COIL. 6. OK TO TERMINATE CONDENSATE TO LAV. TAILPIECE 7. PROVIDE ACCESS TO FAN COIL LARGE ENOUGH TO REMOVE THE EQUIPMENT 8. STILL NEED TO SEE LINE SET AND CONDENSATE DRAINS 9. PROVIDE ACCESS TO FIRE DAMPER |
|
03/09/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO WRAP DUCT NOTE: RECTANGULAR DUCT ONLY HAS 1/2" LINER WHICH DOES NOT MEET THE MINIMUM 4.2 REQUIREMENT THIS DUCT MUST ALSO BE WRAPPED OR REPLACED. |