Permit: T08CM03850

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03850

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/12/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS DO REQUIRE 1 1/2" INSULATION ON ALL
ROUND DUCT.
2. SEE NOTE "R" PAGE M2.
3. INSULATION REQUIREMENTS HAVE BEEN MET.
4. OK TO PROCEED WITH SHEETROCK.
5. PROVIDE A LIGHT & RECEPTACLE FOR SERVICING FAN COIL.
6. OK TO TERMINATE CONDENSATE TO LAV. TAILPIECE
7. PROVIDE ACCESS TO FAN COIL LARGE ENOUGH TO REMOVE THE EQUIPMENT
8. STILL NEED TO SEE LINE SET AND CONDENSATE DRAINS
9. PROVIDE ACCESS TO FIRE DAMPER
03/09/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO WRAP DUCT

NOTE: RECTANGULAR DUCT ONLY HAS 1/2" LINER WHICH DOES NOT MEET THE MINIMUM 4.2 REQUIREMENT THIS DUCT MUST ALSO BE WRAPPED OR REPLACED.