Permit: T08CM03840

Parcel: 12617138B


Addresses:

787 S ALVERNON WY

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/08/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR CEILING TILES
06/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO ROCK SOFFITS MECHANICAL ONLY
05/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. INSTALL RETURN AIR BOOTS PER PLANS
2. PROVIDE EXHAUST FANS FOR RESTROOMS AS PER PLANS
3. SUPPORT CEILING DIFFUSERS
4. PROVIDE OUTSIDE AIR DUCTS SIZED PER PLAN
5. OK PARTIAL CEILING TILES
04/27/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/24/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUSPENDED ROUGH DUCT OK TO PROCEED
2. INSTALL PER DETAILS ON PLANS OR PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS
3. FAN COILS NOT INSTALLED PER CODE
4. ELEC. WIRING NOT PROPERLY CONNECTED, HEAT STRIPS NOT IDENTIFIED, REFER LINES SCRAPING ON SHARP STEEL, CONDENSATE NOT SIZED CORRECTLY.
5. FAN COILS INSTALLED WITHOUT PERMITS