Permit: T08CM03840

Parcel: 12617138B


Addresses:

787 S ALVERNON WY

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/15/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/08/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSULATION OK
2. HAVE CLOSET FLANGE INSPECTED PRIOR TO
SETTING OF STOOLS
04/30/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV THRU ROOF OK
WATER DISTRIBUTION OK

1. NEED TO SEE CORRECT CLOSET FLANGE INSTALLATION PRIOR TO SETTING STOOLS
2. INSULATE PIPING PER PLAN PO.2, 2.2
04/29/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOUTH RESTROOM IN WALL OK
1. SUPPORT OVERHEAD PIPING AT CHANGES OF DIRECTION AND AT CORRECT INTERVALS
2. PROVIDE 2" PERM CAP ON WATER AT THIS RESTROOM SOUTHEAST CORNER ABOVE CEILING
3. NORTH RESTROOM IN WALL OK. RETEST AFTER REPAIR ON VENT ABOVE CEILING
4. PROVIDE HANGERS AT CORRECT INTERVALS ON ALL PIPING THIS RESTROOM
5. PROVIDE CORRECT DRAINAGE FITTINGS FOR EWC DRAIN WITH TEST
03/10/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL PER APPROVED PLAN AND SPEC
2. UNDERGROUND IN WOMENS RESTROOM WITH ABS TEST OK WITH LETTER
3. ADD SUPPORT IN WALLS