Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) DOVE TAIL COLLARS AND FLEX EXHAUST DUCT OK PER LETTER FROM ENGINEER 2) OK FOR CEILING TILES ALL AREAS |
|
| 07/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE GALVANIZED DUCT FOR EXHAUST FANS 2) SEAL FLEX DUCTS AND VAPOR BARRIERS WITH LISTED DUCT TAPE AS PER PLANS 3) SADDLE FLEX DUCTS UP OFF OF CEILING TILES 4) OK FOR PARTIAL TILES |
|
| 07/06/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE TAPS PER PLANS, DOVE TAIL NOT ACCEPTABLE |
|
| 05/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |