Permit: T08CM03832

Parcel: 110035980

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/03/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
03/26/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/24/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. DO NOT OVAL THE RETURN AIR CONNECTION TO THE CEILING PLENUM BOX. SIDE TAP AS PER PLANS.
2. PROVIDE PLENUMS ON SUPPLY DIFFUSERS AS PER PLANS.
3. PROVIDE A LETTER FROM ENGINEER IF CHANGING ANY DETAILS
4. CHECKED CONDENSATE DRAINS STEP UP TO 1" AT 1ST TEE AT UNIT #7 -- ALL OTHERS OK
01/21/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*