Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03824
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTANT HOT TO BE PROTECTED BY 25AMP BREAKER SEE PANEL SCHEDULE E-1 2. NEED UPDATED PANEL SCHEDULE 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 4. NOT SHARING NEUTRALS PROPERLY IN PANEL BECAUSE OF SPLIT BREAKERS 5. SPLIT BREAKERS NOT IN PROPER POSITIONS IN PANEL. HAVE BROKEN REJECTION TABS ON BREAKERS 6. CANNOT OPEN PANEL "B" PAINTED OVER. PANEL "B" IS NOT ON PLANS. |