Permit: T08CM03824

Parcel: 128100560

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03824

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTANT HOT TO BE PROTECTED BY 25AMP BREAKER
SEE PANEL SCHEDULE E-1
2. NEED UPDATED PANEL SCHEDULE
3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
4. NOT SHARING NEUTRALS PROPERLY IN PANEL BECAUSE OF SPLIT BREAKERS
5. SPLIT BREAKERS NOT IN PROPER POSITIONS IN PANEL. HAVE BROKEN REJECTION TABS ON BREAKERS
6. CANNOT OPEN PANEL "B" PAINTED OVER.
PANEL "B" IS NOT ON PLANS.