Permit: T08CM03823

Parcel: 106060120


Addresses:

1265 W ROGER RD #02


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03823

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/22/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OK HANDLE PER PREVIOUS INSP. NOTES
2. GROUND 3/0 WIRE SIZE CUT AT BLOCK WALL, NEED TO REPLACE WITH IRREVERSIBLE TYPE SPLICE OR INSTALL NEW GROUND RODS, MUST REPAIR ASAP AS THIS SYSTEM IS UNSAFE WITHOUT.
03/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FOR USE OF UNITS AS PER DISCUSSIONS WITH LEERAY
NEED TO BE COMPLETED BY 5/1/09 FOR HANDLES
02/26/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/25/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ALL ROOMS 2, 11, 12, 13 OK
HANDLE ON DISCONNECT SERVICE NEED TO BE FIXED
02/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #2 ONLY - FINAL

1. MAIN DISCONNECT HANDLES MISSING -
NEED TO REPLACE ASAP!
2. CONNECT GROUND FAULT PATH TO SERVICE
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
#2:
1) BOND GAS PIPING
2) BEDROOM CIRCUITS TO BE ARC FAULT PER PLANS AND 210.2
3) MAKE UP BATH BAR PER INSTRUCTIONS AND PROTECT CONDUCTOR
4) ONLY ONE CONDUCTOR UNDER TERMINAL GROUND SCREW
5) MAIN SERVICE DISCONNECT INOPERABLE-NO HANDLE
6) NO GROUND PATH OBSERVED AT SERVICE
02/02/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/27/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. OUTSIDE FIXTURES TO BE FLUSH TO WALL TO PREVENT WATER FROM ENTRY
2. INSTALL ALL DEVICES OR PLATES, HOOD AND FIXTURES
01/23/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/21/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
#11
1. MISSING OUTSIDE LIGHT
2. MISSING LIGHT ENTRY HALL
3. MISSING COVER PLATES
4. CLEAN BREAKERS TO READ AMPACITY SETTINGS AND LABEL PANEL PER 408.4