Permit: T08CM03822

Parcel: 105110660

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM03822

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2009 PLUMBING - INTERMEDIATE Approved
05/08/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/27/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED TO REINSPECT FLANGES
OK TO COVER ALL OTHER AREAS
03/26/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEAL JOINTS OF INSULATION W/APPROVED CEMENT PER MANUFACTURES INSTRUCTIONS
2. USE SOLID SUPPORTS IN WALL
03/24/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEE NOTE #8 ON PO.1 PLUMBING SPEC's - NOT INSULATED PER PLAN
2. SUPPORT HORIZONTAL PVC IN WALLS
03/20/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. COPPER SHALL NOT BE BENT OR STRAINED
2. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP
3. PROTECT PVC FROM METAL STUDS
4. PVC TO BE SUPPORTED AT CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
5. VERTICAL PVC TO BE SUPPORTED
6. NO PROVISION MADE FOR INSULATION
7. USE CORRECT SIZE ISOLATORS
8. OK TO INSULATE HOT