Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03806

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/05/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
05/05/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/04/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. RELOCATE DISCONNECT AT HORIZ. UNITS
2. PROVIDE SECONDARY DRAIN ON HORIZ. UNITS
3. PROVIDE PROPER RADIUS ON FLEX 90 DEG. BENDS
4. SUPPORT FLEX OFF OF OTHER TRADES
5. PAINT BLACK RETURN CANS PER PLANS.
03/24/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/23/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE HIGH EFFICIENCY TAPS IN 3 LOCATIONS ON SUPPLY DUCT
2. PROVIDE CONDENSATE PIPING FOR HORIZ. UNIT
3. OK TO INSULATE DUCT
03/19/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/18/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE VIBRATION ISOLATORS PER DETAIL 3
2. NO DOVE TAILS ALLOWED PER MECH. SPEC. DUCTWOR 7
3. PROVIDE AIR SCOOPS PER DETAIL 5 AND MECH. SPEC. DUCT WORK 7
4. SEAL ALL LONGITUDINAL SEAMS PER IECC NOT E3 M2.1
5. PROVIDE ONLY PITTSBURGH LOCK SEAMS PER MECHANICAL SPECIFICATIONS DUCT WORK 5
6. DUCT SUPPORT NOT TO EXCEED 8' PER MECH. SPEC. DUCT WORK 10