Permit: T08CM03803

Parcel: 117030720


Addresses:

820 N 6TH AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03803

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/18/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/09/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CALL BACK FOR REINSPECTION WITH DAN
11/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROUGH UNIT #1
07/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WHY IS THERE A 4 CKT PANEL IN HALLWAY ?
07/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSPECTION FOR UNIT #2, VERIFY 2 CKTS FOR KITCHEN COUNTER TOP RECEPTS. PETR PLANS, NEC
06/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH WALLS ONLY UNIT #2
06/24/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CONTR. TO RECALL INSPECTION - RICK H. INSPECTOR PER CONVERSATION WITH BRIAN (SHAFFER ELEC.)
05/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER OF WALLS
UNIT #4
05/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS EXCEPT HALLWAY-MISSING RECEPTS
2) LOOSE FITTINGS ON CONDUIT FOR PANEL FEEDER
05/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNIT #3 ONLY OK FOR INTERMEDIATE
2) STILL NEED TO INSPECT UNITS 1, 2, & 4
3) OK TO DRYWALL AND GET READY FOR FINALS (UNIT #3) ONLY
05/07/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT 3:
1) NEED PROTECTION PLATES ON WIRING LESS THAN 1 1/4" FROM FRAMING MEMEBER
2) MISSING CIRCUIT UNDER SINK #18 PER PLAN
3) MISSING CIRCUIT ON EAST WALL AT KITCHEN #5 PER PLAN
04/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNIT #5 ONLY
2) WILL APPROVE FINALS ONCE UNITS 1, 2, 3 & 4 ARE APPROVED
02/04/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED TO PROTECT ALL WIRE CIRCUITS IN CEILING AT BEDROOM CLOSET UNIT #05 ONLY
02/02/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTED UNIT #5 ONLY:
1) NEED TO RUN HARDWIRE AND INTER CONNECT SMOKIES IN HALLWAY AND BEDROOMS
2) NEED TO PROTECT ALL WIRES AT HOME RUN CEILING
3) NEED SOME PROTECTION AT HOMERUNS COMING THRU WALL