Permit: T08CM03788

Parcel: 141153540

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM03788

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/05/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND OVER FLUE
EVERYTHING ELSE IS OK
03/03/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. AIR BALANCE OK
2. TESTED DUCT SMOKE DETECTOR
3. EXTEND OVER FLUE MIN. 2' ABOVE
PARAPET WALL & SECURE
4. PERMANENTLY I.D EQUIPMENT WITH SUITE NUMBER & EQUIPMENT NAME OR NUMBER
02/24/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/23/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*