Date Description Inspector Results Comments
02/11/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/04/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/02/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE OUTSIDE AIR HOODS
2. TERMINATE CONDENSATE AT APPROVED LOCATION
3. SIZE CONDENSATE PIPING AS NEEDED 2006 IMC
4. PROVIDE CONDENSATE TRAPS
5. CONDENSATE PIPING SUPPORTS NOT TO EXCEED 4'
6. PAINT CONDENSATE PIPING
7. PROVIDE APPROVED DUCT SUPPORT
(SEE SMACNA STANDARDS)
8. PROVIDE SUN SHIELDS AT FLEX CONNECTORS
9. PROVIDE PROTECTION AT LOW VOLTAGE WIRING (SEALTITE)
10. E.C. UNITS OK
11. PROVIDE COVER PLATE AT HEATER ON UNIT 13
01/27/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
PAINT RTU DUCT PER PLANS