Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM03754
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/04/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
02/02/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE OUTSIDE AIR HOODS 2. TERMINATE CONDENSATE AT APPROVED LOCATION 3. SIZE CONDENSATE PIPING AS NEEDED 2006 IMC 4. PROVIDE CONDENSATE TRAPS 5. CONDENSATE PIPING SUPPORTS NOT TO EXCEED 4' 6. PAINT CONDENSATE PIPING 7. PROVIDE APPROVED DUCT SUPPORT (SEE SMACNA STANDARDS) 8. PROVIDE SUN SHIELDS AT FLEX CONNECTORS 9. PROVIDE PROTECTION AT LOW VOLTAGE WIRING (SEALTITE) 10. E.C. UNITS OK 11. PROVIDE COVER PLATE AT HEATER ON UNIT 13 |
|
01/27/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* PAINT RTU DUCT PER PLANS |