Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T08CM03716
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2009 | ELECTRIC - OUTDOOR LIGHTING | Approved | ||
| 11/20/2009 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE OFFICE FURNITURE CONNECTIONS 2) NEED HANDLE TIES PER 605.7 3) BOXES MORE THAN 1/4" 314.20 4) WOMENS RESTROOM EM LIGHT NOT WORKING 5) PANEL SCHEDULES NOT CLEAR 408.4 6) INTERIOR ONLY-CK DRIVE THRU, ROOF AND PARKING LOT NEXT TIME |