Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
12/22/2009 ELECTRIC - OUTDOOR LIGHTING Approved
11/20/2009 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
1) NEED TO SEE OFFICE FURNITURE CONNECTIONS
2) NEED HANDLE TIES PER 605.7
3) BOXES MORE THAN 1/4" 314.20
4) WOMENS RESTROOM EM LIGHT NOT WORKING
5) PANEL SCHEDULES NOT CLEAR 408.4
6) INTERIOR ONLY-CK DRIVE THRU, ROOF AND PARKING LOT NEXT TIME