Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM03716

Parcel: 115211550


Addresses:

1740 W SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Permit Number - T08CM03716

Inspection Description - ELECTRIC - OUTDOOR LIGHTING

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2009 ELECTRIC - OUTDOOR LIGHTING Approved
11/20/2009 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*
1) NEED TO SEE OFFICE FURNITURE CONNECTIONS
2) NEED HANDLE TIES PER 605.7
3) BOXES MORE THAN 1/4" 314.20
4) WOMENS RESTROOM EM LIGHT NOT WORKING
5) PANEL SCHEDULES NOT CLEAR 408.4
6) INTERIOR ONLY-CK DRIVE THRU, ROOF AND PARKING LOT NEXT TIME