Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2009 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 09/03/2009 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND SERVICE EQUIP. PER 250.92 2. BOND NEUTRAL IN L1 PANEL (SERVICE DISC. MEANS) 3. REMOVE EQUIP. GROUNDS RUN TO L1 FROM CT |
|