Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 12/05/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BRANCH TAPS NOT PER MECH. SPECS. C.2 2. PLENUMS NOT SEALED 3. SEAL VAPOR BARRIER ON ALL FLEX RUNS 4. PROVIDE OBD's IN ALL GRILLES PER REGISTER SCHEDULE 5. COMPLETE PIPING INSULATION 6. PROVIDE FULL 1X RADIUS ON ALL FLEX BENDS 7. PROVIDE FLEX SUPPORT AS NEEDED TO ELIMINATE SAGGING (5' MAX.) |