Permit: T08CM03705

Parcel: 105110670

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/09/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
12/05/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BRANCH TAPS NOT PER MECH. SPECS. C.2
2. PLENUMS NOT SEALED
3. SEAL VAPOR BARRIER ON ALL FLEX RUNS
4. PROVIDE OBD's IN ALL GRILLES PER REGISTER SCHEDULE
5. COMPLETE PIPING INSULATION
6. PROVIDE FULL 1X RADIUS ON ALL FLEX BENDS
7. PROVIDE FLEX SUPPORT AS NEEDED TO ELIMINATE SAGGING (5' MAX.)