Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T08CM03703

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2009 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
06/04/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
06/03/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
05/19/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
CHECKED REMAINDER OF INSULATION IN TRENCH
OK TO BACKFILL MAIN TRENCH
04/27/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
PIPE INSULATION NORTH SIDE
04/23/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
04/22/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
04/21/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSULATING SOUTH OF OFFICE, SPRAY FOAM IN TWO LAYERS TO ACHIEVE MIN. 1 1/2" THICKNESS SPECIFIED
04/17/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
04/15/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSULATION AT OFFICE AND CLUBHOUSE OK
04/13/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) AS ? ON P-1 THE REST OF THE UNDERGROUND PIPING IS INSTALLED AND TESTED
2) SOUTH SIDE INSUBTED OK AS INITIALED
04/07/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
CHECK & PROVIDE THICKNESS OF INSULATION SPECIFIED
NEED TO SEE STAMPED DETAIL FOR INSULATION
SPECIFICATION AND LETTERS FOR CW PIPING & INSULATION
04/03/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSULATING PER ENGINEERS DETAIL
04/02/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
03/27/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
PIPE INSULATION ON PREVIOUSLY TESTED SECTION OK
PROVIDE LETTER FOR DELETION OF CW INSULATION
03/24/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
CPVC YARDWATER REPIPE IN BRACKETED AREA ON P-1 AS INITIALED OK TO INSULATE.
RECALL FOR INSPECTION AFTER UNDERGROUND INSULATION