Permit: T08CM03700

Parcel: 141312480

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T08CM03700

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2008 BUILDING - FINAL Approved IVRS - Inspection :*
12/18/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUB PANEL 15 GENERAL LIGHTING CIRCUITS ON LOOKS LIKE ROMEX FEEDER CABLE #8 CU.-IS ONLY GOOD FOR 40 AMPS, SEE BREAKERS IN SERVICE PANEL