Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03694
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/14/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LETTER FROM ARCHITECT STATES NEW 40 AMP BREAKER TO BE INSTALLED 2) FINISH LIGHT IN CONTROL CLOSET |
|
09/13/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) IT APPEARS PREVIOUS INSPECTION ITEMS CORRECTED, R. HOLLANDER TO VERIFY AT NEXT INSPECTION |
|
08/10/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* MENS SAUNA: 1) OPEN WALL TO SEE CONDUIT INSTALLATION AS DISCUSSED 2) FILL UNUSED OPENING IN CONTROL BOX 3) CORRECTLY IDENTIFIED CONDUCTOR COLORS-RACEWAY ENTIRE LENGTH 250.119 AND CABLE 200.4 4) NEED DIAGHRAM #2 FOR MAKE UP WIRING 5) SUPPORT CONDUIT AND M/C PER CODES-DO NOT LAY ON PIPES ON GRID 6) LIGHT FIXTURE NOT SUPPORTED IN GRID AT ALL 7) FANS TO BE LISTED FOR LOCATION SERVED 8) PLANS NOT DIRECTLY REFLECTIVE OF INSTALLED WORK |