Permit: T08CM03670

Parcel: 141314830

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM03670

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
#3 BELOW (NEED STATIC H3 TEST ON DWV)
12/22/2008 PLUMBING - INTERMEDIATE Denied 1) F.H.A STRAPS AT 1" H20 LINE (STUD)
2) MOVE ALL PEX H20 LINES 12" FROM CAN LIGHTS
3) NO H20 IN DWV TEST
4) NO PRESS ON POTABLE H20 LINES
5) DBL LAV NOT PLUMBED PER CODE, WEST LAV. VENT CONNECTION BELOW THE TRAP-2" TRAP ARM REQUIRES A 2" TRAP