Permit: T08CM03660

Parcel: 11615088L

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03660

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
05/13/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OUTSIDE AIR MUST BE UP STREAM OF DUCT SMOKE DETECTOR
2) CORRECT PRIOR TO FINAL
3) OK FOR TILES MECH. ONLY
05/11/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE A PANDUIT STRAP OVER ALL UNLISTED DUCT TAPE
USE ONLY UL181 TAPES AND MASTIC
NEED LIGHTS ON