Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03659
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
05/13/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OUTSIDE AIR MUST BE UP STREAM OF DUCT SMOKE DETECTORS 2) CORRECT PRIOR TO FINAL 3) PROVIDE TRANSFER DUCTS PER PLANS 4) OK FOR TILES MECH. ONLY |
|
05/11/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE A PANDUIT STRAP OVER ALL UNLISTED DUCT TAPE USE ONLY UL181 TAPES AND MASTIC |
|
02/06/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/03/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |