Permit: T08CM03637

Parcel: 14024079B


Addresses:

1401 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE RECALL INSP. CONTR. ON SITE TO
REMOVE X-FORMER COVER.
2. NEUTRAL TO BE BONDED ON SECONDARY SIDE
OF X-FORMER, ONLY ONE TIME, EITHER IN X-FORMER OR SEC. DISC. SW. BUT NOT BOTH - PER 250 NEC
12/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PROVIDE OVERCURRENT PROTECTION FOR SECONDARY
X-FORMER FEEDERS TO PANEL LB PER 408.36 B & D