Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE RECALL INSP. CONTR. ON SITE TO REMOVE X-FORMER COVER. 2. NEUTRAL TO BE BONDED ON SECONDARY SIDE OF X-FORMER, ONLY ONE TIME, EITHER IN X-FORMER OR SEC. DISC. SW. BUT NOT BOTH - PER 250 NEC |
|
| 12/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE OVERCURRENT PROTECTION FOR SECONDARY X-FORMER FEEDERS TO PANEL LB PER 408.36 B & D |