Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM03636
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/12/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) A/C UNIT ON ROOF WAS INSTALLED WITHOUT A PERMIT 2) THERE ARE NUMEROUS CODE VIOLATIONS 3) PROVIDE A FRESH AIR INTAKE AND BALANCE PER PLANS 4) STEP UP CONDENSATE TO 1" AFTER 1ST TEE AND TERMINATE DIRECTLY OVER THE DOWN SPOUT 5) EXTEND DOWN SPOUT TO THE DIRT 6) SUPPORT ELECTRIC CONDUITS 7) MARK UNIT DATA WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY 8) PROVIDE 1/8" PER FT SLOPE AT ALL SECTIONS OF CONDENSATE DRAIN LINE |
|
07/29/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |