Permit: T08CM03627

Parcel: 140150470


Addresses:

1902 E VIRGINIA ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T08CM03627

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2009 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/27/2009 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXT. SIDING SHALL BE NAILED AT 8" ON CENTER THRU-OUT
2) OK TO INSULATE AND SHEETROCK
3) INSTALL FAN IN EXISTING BATHROOM
4) RE-ROUTE WATER LINE
05/26/2009 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SIDING SHALL BE NAILED 8" ON CENTER TOP AND BOTTOM
2) CUT FOR WINDOW AND INSTALL IN EXISTING BEDROOM
3) PROTECT ALL WIRES CLOSER THAN 1 1/2" FROM FACE OF STUDS
4) GROUND ALL METAL BOXES
5) CAN'T REDUCE WIRE FROM 12-2 TO 14-2
05/07/2009 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL SIDING WITH 7 GALV. MINIMUM 8" ON EDGES AND 12" ON CENTER IN FIELD
2) REMOVE ALL SHEETROCK AND INSULATION FOR INSPECTION OF ELECTRICAL WIRING
3) PLUMBING WORK SUB-STANDARD, HIRE PLUMBER TO REDO ALL PLUMBING
4) CHECK APPROVED DRAWING FOR REQUIRED CONNECTION BETWEEN PLATES AND CONCRETE