Permit: T08CM03626

Parcel: 136244460

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/28/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/21/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) STILL MISSING OUTDOOR EM ON EAST END OF BLDG
2) FINISH WIRING X-RAY EQUIPMENT
07/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CHECK WITH BLDG INSPECTOR FOR TCO
2) MISSING EM LIGHT IN CONFERENCE ROOM
3) ALL MEDICAL EQUIPMENT TO BE LISTED, VERIFY LISTING OF EQUIPMENT INCLUDING X-RAY EQUIPMENT
07/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) 2 EXITS NOT WORKING
2) NEED REVISED PLANS FOR CHANGES AND NEED PLANS FOR FIRE ALARM SYSTEM
3) MISSING FLOOR RECEPTS AND WORK STATIONS
4) MISSING EM LIGHT IN CONFERENCE ROOM
5) ONE OUTDOOR EM LIGHT NOT WORKING
6) ALL MATERIAL EQUIPMENT TO BE LISTED
7) X-RAY EQUIPMENT TO BE LISTED. DO NOT SEE LISTING LABEL ON X-RAY EQUIPMENT. PLEASE VERIFY LISTING OF X-RAY EQUIPMENT. MAY NEED TO HAVE FIELD EVALUATION IF EQUIPMENT IS UNLISTED
07/01/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) DO NOT SCHEDULE FINAL INSPECTION UNTIL ELECTRICAL CONTRACTOR IS READY FOR INSPECTION
2) NOT READY INSPECTIONS WILL RESULT IN A RE-INSPECTION FEE