Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08CM03607
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/08/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/16/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/12/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK SECONDARYS TEP X-FORMER TO SES 2. CONV. OUTLET AT FIELD #2 |
|
12/11/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK U.G PVC FOR REMAINDER OF LIGHTPOLES PULL BOXES NOT COMPLETE 2. HDPE FOR SECONDARYS TO SES NOT LISTED AS PER 353.6 AND 353.120 NEC |
|
12/01/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* A3-TRENCH EXISTING 1 - 2 1/2" --- 1 - 3" ADDING 2 - 2" TO POLE B3 OK |
|
11/25/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK U.G PVC CONDUIT AT "B4" TO "A4" TO OUTSIDE SES AND "B2" TO "A2" TO SES #7 PULL BOX "A1" TO ELECTRIC ROOM |