Permit: T08CM03597

Parcel: 105102430

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/29/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/27/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE AUDIO AND VISIBLE ON D.S.D
2) PROVIDE AIR BALANCE REPORT
3) ALL OTHER ITEMS DATED 7/22/09 COMPLETE
07/22/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) RELOCATE DISCONNECTS BLOCKING ACCESS TO A/C 1 & 5 2) SERVICE A/C UNITS PER MANUFACTURERS INTALL INSTRUCTIONS
3) FOIL TAPE NOT APPROVED FOR OUTDOOR USE. YOU CAN USE POP RIVETS ON DRYER VENT AND OUTDOOR TAPE
4) A/C UNITS OVER FUSED
5) AUDIBLE AND VISIBLE ALARMS NOT WORKING