Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T08CM03597
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
07/20/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) HAVE REVISED PLAN STAMPED BY PLAN REVIEW |
|
07/15/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) CLOSET FLANGES OK 2) PROVIDE GAS PLAN 3) GAS PIPING TO WATER HEATER PAINTED BEFORE INSPECTION 4) WATER HEATERS NOT INSTALLED PER PLAN |
|
05/28/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 60 PSI TEST OK PROVIDE 1. REDLINES 2. MATERIAL SPECS 3. WELDER CERT SOV's SHOWN ABV ROOF AT DRYER AND WH DROP |