Permit: T08CM03597

Parcel: 105102430

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM03597

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/19/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
BELOW FLOOR PIPING W/TEST OK IF ENGINEER APPROVES MATERIAL CHANGE SEE SPEC 15415

INSTALL ABV SLAB TEST FITTINGS AND OR MAKE OTHER PROVISIONS AND RETEST SO THAT NO JOINT GOES UNTESTED
INSTALL P1 TO C1 TRANSITION COUPLINGS IF USING CASTIRON ABV FLOOR