Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM03597
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ABOVE GRID, EXCEPT TERM TO PROSECTORS |
|
07/15/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT MC PER 330 NEC, 300.11 NEC 2) SUPPORT FIXTURE TO GRD. SCREWS OR CLIPS |