Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM03581
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/06/2009 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) HAVE AS BUILTS APPROVED BY PLAN CHECK |
|
06/01/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED CITY APPROVED PLANS FOR PHOENIX SYSTEM, IF (INSTALL BOOKLET) IS TO BE USED INSTALL PER DRAWING 2) 1" PIPE FOR H20 SUPPLY REQUIRED BY BOOK 3) 4" PLASTIC PIPE TO BE SCHEDULE 40 NOT FOAM CORE TYPE 4) TWO DRAINS TIED TOGETHER BACK CHECK NOT APPROVED FOR THIS INSTALL, EXPANSION TANK REQUIRED BY DRAWING 5) ALL CIRC. PUMPS TO HAVE INTREAL BACK CHECK 6) STANDING H20 IN FURNACE, SEASONAL NOT SHOWN ON PLAN 7) PROTECTION FROM AUTO 8) IS H20 TO FURNACE TO BE POT H20M, OR GYLCOL TREATED 9) ROMEX NOT PROTECTED (USE) |
|
05/28/2009 | BUILDING - FINAL | Partial Approval | 1) QUESTION ON H20 SYSTEM (WITH ANTI FREEZE) 2) BAD GFCI TEST OPEN EXT/REVERSE POLARITY 3) PHOTO VOLTIC REQUIRES INSPECTION PERMIT |
|
02/24/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |