| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 11/20/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROPERLY SUPPORT CONDENSATE DRAINS EVERY 4' 2) PAINT EXPOSED PVC WITH LATEX PAINT 3) FINISH CONNECTING UNITS ON ROOF 4) PROVIDE AIR BALANCE REPORT |
|